PARTIAL DISCHARGE MEASUREMENTS ON BÖNING MODEL
Igor Kròák
Well-known abc circuit, Gemant-Phillipow three capacitors model,
however proved for industrial purposes, is a too simplified representation
of the actual behaviour of the dielectric. This can be better described with
the aid of Böning model considering during the discharge processes also
the charge movement along the surface of cavities. A laboratory model of this
type has been constructed and both voltage across the cavity and number of
discharges were measured and compared with the theoretical assumptions.
Keywords: apparent charge, Böning model, ignition voltage, partial discharge, remanent voltage, return voltage
|