IMPROVING POWER SYSTEM TRANSIENT STABILITY WITH AN OFF-CENTRE LOCATION OF SHUNT FACTS DEVICES
Sidhartha Panda - Ramnarayan N. Patel
Shunt Flexible AC Transmission System (FACTS) devices, when placed at the mid-
point of a long transmission line, play an important role in controlling the
reactive power flow to the power network and hence both the system voltage
fluctuations and transient stability. This paper deals with the location of a
shunt FACTS device to improve transient stability in a long transmission line
with predefined direction of real power flow. The validity of the mid-point
location of shunt FACTS devices is verified, with different shunt FACTS devices,
namely static var compensator (SVC) and static synchronous compensator (STATCOM)
in a long transmission line using the actual line model. It has been observed
that the FACTS devices, when placed slightly off-centre towards sending-end,
give better performance in improving transient stability and the location
depends on the amount of local/through load.
Keywords: FACTS, STATCOM, SVC, transient stability
|